Load Testing Your Battery
Use this same procedure for VRLA DRY CELL batteries and Flooded batteries:
- Recharge if the open circuit voltage is below 75%.
- If you have an adjustable load tester, set the load at 3 to 3.5 times the 20-hour rate.
- Apply the load for 15 seconds. The voltage should stabilize above 9.6 volts while on load.
- If the battery has a CCA rating, you can apply a load equal to ½ the rating for 15 seconds. The voltage should stabilize above 9.6 volts while on load.
- To apply a more determined test, you may apply a load equal to 100% of the rated CCA or 5 to 6 times the 20-hour rate for 30 seconds. The voltage should stabilize above 7.2 volts while on
- If below 9.6 volts (7.2 volts for the 100% CCA test), recharge and repeat the test. If below 9.6 volts (7.2 volts for the 100% CCA test) again, replace the battery.